日韩女人性开放视频,性刺激的大陆三级视频,国产人碰人摸人爱视频,电家庭影院午夜

歡迎您訪問:瑞昌明盛自動化設備有限公司,我司將竭誠為您服務!
1391-DES15-DI-AQB擴展驅動模塊

主頁 > 產品中心 > RELIANCE

1391-DES15-DI-AQB擴展驅動模塊

類目:RELIANCE
型號:1391-DES15-DI-AQB
全國服務熱線:15270269218
手機:15270269218
微信:15270269218
QQ:3136378118
Email:3136378118@qq.com

在線咨詢
產品詳情
產品廣泛應用于冶金、石油天然氣、玻璃制造業(yè)、鋁業(yè)、石油化工、煤礦、造紙印刷、紡織印染、機械、電子制造、汽車制造、塑膠機械、電力、水利、水處理/環(huán)保、鍋爐供暖、能源、輸配電等等。
主營DCS控制系統(tǒng)備件,PLC系統(tǒng)備件及機器人系統(tǒng)備件,
優(yōu)勢品牌:Allen Bradley、BentlyNevada、ABB、Emerson Ovation、Honeywell DCS、Rockwell ICS Triplex、FOXBORO、Schneider PLC、GE Fanuc、Motorola、HIMA、TRICONEX、Prosoft等各種進口工業(yè)零部件

1391-DES15-DI-AQB擴展驅動模塊 1391-DES15-DI-AQB擴展驅動模塊 1391-DES15-DI-AQB擴展驅動模塊 1391-DES15-DI-AQB擴展驅動模塊
外部電壓調節(jié)變阻器(端子R1和R2):端子R1和R2用于連接電壓調節(jié)變阻器。
這個變阻器提供調節(jié)發(fā)電機電壓的±10%名義上的它作為面板安裝的單獨項目提供。連接變阻器的導線連接到端子R1和R2??缃訉Ь€必須連接在變阻器端子2和變阻器1之間如圖6所示。
連接至無功電壓降端子CT _、CT1和CT5并聯(lián)運行:當發(fā)電機并聯(lián)運行時,安裝
B相電流互感器從每個發(fā)電機引出,并連接為跟隨-電流互感器(1 A次級):將次級引線連接到CT-公共和CT1。確保保持正確的極性。制作確??缃悠髟谔峁r已從CT上拆除CT1。
-電流互感器(5 A次級):將次級引線連接到CT公共和CT5。確保保持正確的極性。制作
確??缃悠髟谔峁r已從CT上拆除CT1。
無功電壓降或交叉電流補償:調節(jié)系統(tǒng)可在無功狀態(tài)下并聯(lián)運行
電壓下降或交叉電流補償模式。按無功電壓下降或交叉電流補償。
-無功電壓降:將電流互感器連接到各自的調節(jié)器(見圖7)。
-交叉電流補償:對于交叉電流,連接每個CT至其各自的調節(jié)器。然后連接? 尼什? rst CT to第三個CT的開始等繼續(xù),直到所有CT連接到串聯(lián)并連接? 從后一個CT結束到? rst CT
-并聯(lián)交叉電流補償應用包括:對于兩臺或多臺發(fā)電機,如果所有發(fā)電機并不總是在公共汽車上。如果不使用開關,系統(tǒng)將引入電壓降,這將使輸入發(fā)電機的電壓:? 在之前完成平行。這是由于發(fā)電機并聯(lián)CT空載,而不是提供其補償信號,但允許電壓降發(fā)生在其上。理想情況下,開關是發(fā)電機上的輔助開關斷路器閉合時斷開的輸出斷路器。)對于單相傳感,端子為E1和E3。見圖2和圖3。
2) 那個? 發(fā)電機運行時,eld不得打開、短路或接地。
3) 外部電壓調節(jié)器端子1和2之間必須有跨接導線。
4) 輸入功率標準KCR 760電壓為120 Vac;可選240伏交流電。大限度
120伏交流輸入的連續(xù)輸出為65伏直流電,240伏交流輸入為125伏直流電??匆妶D4和圖5。
5) 并聯(lián)運行的發(fā)電機需要電流互感器。連接如圖所示:1 A電流互感器和無功電壓降
補償參見圖2和圖3。
6) 根據(jù)適用的電氣規(guī)范將中性點接地External voltage adjust rheostat (terminals R1 and R2): Terminals
R1 and R2 are provided for connection of the voltage adjust rheostat. The
rheostat provides adjustment of the regulated generator voltage ±10% of 
nominal. It is provided as a separate item for panel mounting. Connecting
wires from the rheostat attach to terminals R1 and R2. A jumper wire
must be connected between rheostat terminal 2 and rheostat terminal 1 as
shown in Figure 6.
Connection to reactive voltage droop terminals CT?, CT1, and CT5
Parallel operation: When generators will be operating in parallel, install
the current transformer in Phase B from each generator and connect as
follows:
- Current transformer (1 A secondary): Connect secondary leads to
CT? common and CT1. Be sure to maintain correct polarity. Make
certain the jumper, when supplied, is removed from across CT? and
CT1.
- Current Transformer (5 A secondary): Connect secondary leads to
CT? common and CT5. Be sure to maintain correct polarity. Make
certain the jumper, when supplied, is removed from across CT? and
CT1.
Reactive voltage droop or cross-current compensation: The regulating
system may be connected for parallel operation in either the reactive
voltage droop or cross-current compensation mode. Connect according to
either reactive voltage droop or cross-current compensation.
- Reactive voltage droop: Connect the current transformer to the
respective regulator (see Figure 7).
- Cross-current compensation: For cross-current, connect each CT
to its respective regulator. Then connect the ? nish of the ? rst CT to
the start of the third CT, etc. Continue until all CTs are connected in
series and connect the ? nish of the last CT to the start of the ? rst CT
(see Figure 8).
- On parallel cross-current compensation applications consisting
of two or more generators, use a unit/parallel switch if all the
generators are not always on the bus. If the switch is not used,
a voltage droop will be introduced into the system, which will
cause the voltage of the incoming generator to ? uctuate prior to
paralleling. This is due to the unloaded generator parallel CT not
supplying its compensating signal, but allowing a voltage drop to
occur across it. Ideally, the switch is an auxiliary on the generator
output circuit breaker that opens when the breaker is closed.) For single-phase sensing, terminals are E1 and E3. See Figures 2 and 3.
2) The ? eld must not be opened, shorted or grounded while the generator is operating.
3) The external voltage adjust must have a jumper across its terminals 1 and 2.
4) Input power standard KCR 760 voltage is 120 Vac; optional 240 Vac. Maximum
continuous output is 65 Vdc for a 120 Vac input and 125 Vdc for a 240 Vac input. See
Figures 4 and 5.
5) A current transformer is required for generators operating in parallel. The connection is shown on this drawing: 1 A current transformer and reactive voltage droop
compensation. See Figures 2 and 3.
6) Ground the neutral in accordance with applicable electrical codes